Marine Wire

Even the experts have to check occasionally on the correct gauge of wire for a given marine DC load. The simplest method we’ve found uses the charts below.

  • Select either the 10% or 3% voltage drop chart, based on the type of load you are running.

  • Next, find the current consumption of the load on the vertical axis of the chart.

  • Find the length of the circuit on the horizontal axis of the chart, noting that the length is the “round trip” distance from the panel or battery to the load and back.

  • The color of the graph at the intersection denotes the gauge of wire to use.


 

We've included copper wire specifications which comply with the AWG standards at the bottom. Of particular interest is the equation: 

Voltage Drop = Current x Length x Ohms per foot

This simple equation allows you to calculate the voltage drop for a circuit of any length and any current flow, if you know the resistance of the wire. Finally, note that the amp capacity of the wire curtails using very short lengths of wire for large current flows, as show by the "flat tops" of the 10% chart areas.

Wire Gauge Color Code Colors in above charts correspond to AWG wire sizes.

 

These simple, proprietary graphs assume:

1.105ºC insulation rating: All Ancor wire uses 105ºC insulation rating. Lower temperature insulation cannot handle as much current (the flat tops on the 10% graph would be lower than shown)

2. AWG wire sizes: Not SAE All Ancor wire uses AWG wire sizes. SAE wire sizes are 6%-12% smaller, carry proportionally less current, and have greater resistance

3. Wires are not run in engine spaces: Maximum current is 15% less in engine spaces, which are assumed to be 20¼C hotter than nonengine spaces (50¼C vs. 30¼C).

4. Conductors are not bundled: If three conductors are bundled, reduce maximum amperage by 30%. If 4-6 conductors are bundled, reduce maximum amperage by 40%. If 7-24 conductors are bundled, reduce amperage by 50%.

 AWG Wire Specs

Wire Size (AWG) Nominal OD Weight per 1000' Cir.Mil. Area Square mm Ohms per 1000' Max Amps
18 7/64" 12# 1,600 0.823 6.48 20
16 1/8" 16# 2,600 1.31 4.00 25
14 9/64" 23# 4,100 2.08 2.5 35
12 5/32" 31# 6,500 3.31 1.75 45
10 7/32" 44# 10,500 5.26 0.98 60
8 5/16" 86# 16,800 8.37 0.62 80
6 11/32" 18# 26,600 13.30 0.40 120
4 13/32" 178# 42,000 21.15 0.24 160
2 15/32" 277# 66,500 33.62 0.157 210
1 17/32" 350# 83,690 44.21 0.127 245
1/0 9/16" 437# 105,600 53.49 0.099 285
2/0 5/8" 549# 133,000 67.43 0.077 330
3/0 11/16" 675# 167,800 85.01 0.062 385
4/0 13/16" 837# 211,600 107.20 0.049 445

To complete your project, don’t forget:
  • Heat Shrink tubing
  • Wire-strippers, cutters, and crimpers
  • Terminals: ring, spade or butt connectors
   Company History
   Mission Statement
   Press Room
   Careers at West Marine
   Affiliate Program
   Annual Catalog
   Store Locator
   And More...
   Stock Price
   Press Releases
   SEC Filings
   Email Alerts
   Analyst Coverage
   Management Team
   Financial FAQ
   And More...
   Terms Of Use
   Returns/Exchanges
   Privacy Policy
   Contact Us
   Site Map
   Annual Catalog
   Product Recalls
   And More...
Product offering and prices listed on this website (www.westmarine.com) are limited to Internet and phone orders (1-800-BOATING). Prices on periodic web-only specials apply only to Internet orders. Product offering and/or prices may vary at West Marine retail stores. ©2009 West Marine | All Rights Reservedpics11